Fire door compliance reports for the AESMR

Fire door records for Victoria's annual essential safety measures report: what the AESMR must state, when it is due, and the records an owner must hold.

The annual essential safety measures report (AESMR) is the owner’s yearly statement that every essential safety measure in the building, fire doors included, has been inspected, tested and maintained as required. A fire door compliance report is the evidence behind that statement for the doors: a door register, the results of each routine, and the defects still open. The provider who prepares those records is an independent business engaged directly by the owner or manager; this site only passes on the enquiry.

Illustrative photo for Fire door compliance reports for the AESMR

What does the AESMR have to state?

Part 15 of the Building Regulations 2018 sets the contents. The report must:

  • use the regulator’s approved form
  • be signed by the owner of the building
  • state the address of the building
  • include details of any inspection report made under the Building Act 1993 about an essential safety measure
  • say, where it applies, that the owner is following AS 1851-2012 instead of the frequencies on the permit or determination
  • state that the owner has taken all reasonable steps to ensure each measure is operating, has been maintained so it fulfils its purpose, and has been inspected, tested and maintained in line with the Act and the Regulations

The Building and Plumbing Commission publishes the approved AESMR template, described as the form owners or their authorised agents use to confirm that essential safety measures have been inspected, tested and maintained.

When is the AESMR due?

Building When the report must be prepared
Measures required by an occupancy permit or maintenance determination Within 28 days before each anniversary of the first permit or determination that required a measure
Building constructed before 1 July 1994, measures required under earlier law Within 28 days before 13 June each year

Scheduling the yearly door routine a few weeks before this date means the results are current when the report is signed.

Records the owner must be able to produce

The owner has 24 hours to make these available at the building once a request comes from the municipal building surveyor or from the fire authority’s chief officer:

  1. every AESMR prepared in the 10 years before the request
  2. all maintenance schedules for the building’s essential safety measures
  3. all maintenance determinations requiring a measure to be provided
  4. the records of every inspection, test and maintenance task, repairs included

Failing to produce them carries a penalty under the regulations. The BPC guide to essential safety measures adds that non-compliance can lead to an infringement notice from the council or the fire authority, and to prosecution.

What a good fire door compliance report contains

Section Contents
Door register Every fire door, smoke door and solid core door with a location reference, type and photo
Requirement The permit, determination or schedule line that applies to each door
Results Date, routine performed, result per door, and who did it
Defects Each fault, its risk, the action recommended and the date it was closed
Exclusions Doors not reached, with the reason and the plan to reach them

A defect register that shows when each item was closed out gives the owner something solid to point to when signing the statement that all reasonable steps were taken.

Why insurers ask about these records

A 2026 article published by FPA Australia, written by an insurance broker, says insurers increasingly request essential safety measures reports and defect registers when policies are placed or renewed. Clean door records with closed-out defects are easier to hand over than a folder of loose invoices.

Who signs, and who prepares?

The signature on the AESMR must be the owner’s. According to the BPC, an owner can give written authority to an agent, for example the fire door or ESM contractor who keeps the door register, to fill in the report. In an apartment building, the owners corporation must repair and maintain common property and its fixtures under the Owners Corporations Act 2006, so its manager is often the person who coordinates contractors and gets the report signed.

What a careful report writer will not do

  • Mark a measure as maintained when the records do not show it.
  • Leave open defects off the report to make it read cleanly.
  • Pre-sign or backdate inspection records.
  • Write the report without a copy of the permit, determination or schedule for the building.

Cost

For a small commercial building, a published Melbourne guide puts the AESMR at $200 to $450 per report before GST, covering the report only, with each measure’s servicing charged separately. Larger strata and multi-storey buildings are quoted individually. The fire door inspections behind it are listed in the same guide at $25 to $75 per door. More detail is in the fire door cost guide.

How it fits with the door work

The report draws on routine fire door inspections, the smoke door and seal checks and the records from fire door repairs. Owners in older blocks in St Kilda and Fitzroy often find the pre-1994 date applies to some measures and a permit date to others.

What to do next

Find your last AESMR and the building’s permit or schedule, then ask for help with fire door compliance records and give the report’s due date.

Send a job enquiry

Frequently asked questions

Who signs the annual essential safety measures report?

The owner of the building. The regulator notes the owner can authorise an agent such as a maintenance contractor to complete it, but the statement that reasonable steps were taken is the owner's.

When is the AESMR due?

For measures required by an occupancy permit or maintenance determination, it is prepared in the 28 days before each anniversary of the relevant date. For pre-1994 buildings it falls in the 28 days before 13 June each year.

How long do we need to keep AESMRs?

The owner must be able to produce every AESMR from the previous 10 years, along with the maintenance schedules, determinations and maintenance records, within 24 hours of a request from the municipal building surveyor or fire authority.

Is there an official AESMR form?

Yes. The Building and Plumbing Commission publishes an approved template, and the report must be in the approved form.

What if some fire door defects are still open when the report is due?

Record them honestly with the action planned and the expected completion date. A report that hides open defects puts the owner in a worse position than one that shows the steps being taken to close them.