Smoke door and seal inspections
Smoke doors and their seals in Melbourne apartment corridors, lobbies and offices: how they differ from fire doors, what fails, and what an inspection covers.
Smoke doors slow the spread of smoke along corridors and into lobbies and stairs, and they only work when they close fully and the seals around them are intact. In Victoria, smoke doors and their self-closing, automatic closing and latching mechanisms are a separate essential safety measure from fire doors, so they need their own entries in the inspection records. Inspections booked after an enquiry here are done by an independent provider, whose report and pricing are their own.

How is a smoke door different from a fire door?
A fire door is a fire-resistant doorset with a tested fire rating. A smoke door is there to limit the passage of smoke, and its seals do much of the work. Some doors do both jobs. Schedule 8 of the Building Regulations 2018 lists them as different items: fire doors in one line, smoke doors and their closing and latching mechanisms in another, and solid core doors with their closing mechanisms in a third.
AS 1851, the standard most Victorian maintenance schedules call up for routine service, covers smoke doors as well as fire doors, and FPA Australia’s Inspect and Test accreditation treats the two as one category of work.
Where smoke doors are found
- corridor doors part way along long apartment and hotel corridors
- doors between lift lobbies and corridors
- doors into stairs that are not fire-isolated
- some office and health building doors that divide smoke compartments
The approvals for your building say which doors are smoke doors. If the paperwork is missing, a provider can still list every self-closing door, but only the occupancy permit, maintenance determination or maintenance schedule settles which ones are required.
What fails on smoke doors
| Item | Problem | Effect |
|---|---|---|
| Perimeter seals | Painted, torn, missing, or compressed flat | Smoke passes around the door |
| Meeting stiles on double doors | Seals worn or the doors closing out of order | Gap left down the centre |
| Bottom of the door | Gap grown by new flooring or wear | Smoke passes under the door |
| Closer | Too weak to close against corridor air pressure | Door rests partly open |
| Hold-open | Wedged, or a magnet that no longer releases | Door stays open during an alarm |
| Vision panels | Cracked or replaced glazing | Smoke and heat path through the door |
Painting is an easy fault to miss. A common-area repaint can coat every brush and rubber seal in a corridor in one afternoon, and the doors then close but no longer seal.
What an inspection covers
The provider walks each smoke door and records:
- Whether the door closes fully from the open position, and latches where it is meant to.
- The condition and continuity of the seals on the head, jambs and meeting edges.
- The gap at the bottom and around the edges compared with what the doorset allows.
- Any hold-open device and whether it releases as designed.
- Damage to the leaf, glazing and frame.
Where a smoke door is also a fire door, the fire door inspection checks apply as well, and the two results should be recorded against one door reference rather than two.
Repairs that usually follow
Seal replacement is the most common outcome. A careful provider fits seals of the type specified for the door rather than a generic weather strip, and does not trim seals to make a binding door close. Closer adjustment comes next, especially on doors that face lift shafts or open stairs, where air pressure works against the closer. Doors with leaf or frame damage move to fire door repairs or, for doorsets beyond repair, to replacement.
Rules and records
The building owner must keep every essential safety measure working and keep the records of inspection, testing and repair. The Building and Plumbing Commission notes that occupiers have a separate duty to keep exits and paths of travel to exits accessible, functional and clear of obstructions. For an apartment building, that makes a smoke door wedged open with a chair a problem for the occupier as well as the owners corporation.
What a careful inspector will not do
- Treat a door as compliant because the seals look new, without checking the seal type.
- Leave a hold-open device in place that does not release on alarm without reporting it.
- Record a door as passed when residents’ belongings stop it closing.
Cost
Smoke doors are usually inspected on the same visit as fire doors and priced per door. A published Melbourne guide puts fire door inspection at $25 to $75 per door, and smoke doors tend to be quoted in the same way. Seal replacement is quoted after the inspection. See the cost guide for fire door work in Melbourne for what to ask.
Local buildings
Smoke door work is concentrated where long internal corridors are common: towers in the Melbourne CBD and Docklands, and newer apartment blocks in Footscray.
What to do next
Note which corridors and lobbies have self-closing doors, then get a smoke door inspection quoted for your building.
Frequently asked questions
- Are smoke doors the same as fire doors?
No. Victoria lists them as separate essential safety measures. A smoke door limits the spread of smoke, mainly through its seals and closing hardware, while a fire door is a fire-resistant doorset. Some doors serve as both.
- Why are painted smoke seals a problem?
Paint stiffens brush and rubber seals so they no longer close the gap around the door. The door may still shut, but smoke can pass around it. Seals that have been painted are normally replaced.
- Can smoke doors be held open?
Only by devices approved for the building that release on a fire alarm. Doors held with wedges, chairs or hooks are a defect, and keeping exits and paths of travel clear is also a duty of the occupier.
- Are smoke doors inspected at the same time as fire doors?
Usually, yes. Providers commonly inspect both on one visit, and doors that are both fire and smoke doors should have one combined record rather than two separate entries.